Expertise in determining
Partial Discharge (PD) signals in noisy electrical
environments
- PD-LSGS手持式开关柜局放检测仪测试仪 Handheld Switchgear PD Detector
- PD-LSG1 便携式开关柜局放检测和定位测试仪Switchgear PD Detection & Location
What is Partial Discharge?
什么是局放
‘Electrical discharge that does not completely bridge the
space between two conducting electrodes’
Where in insulation does PD
occur? 局放产生的位置
What are the effects of PD? 局放会带来什么危害
Individual discharges are low energy but they are very localised and can be very repetitive.
Damage is caused by;
Mechanical – Ionic bombardment
Thermal – Local heating at discharge site
Chemical – Discharge energy breaks chemical bonds
Classification of PD
局放的等级
Switchgear PD can be classified into 3 distinct
types
Corona – Ionization of fluid (air)
surrounding conductor – usually visible.
(Surface)
Tracking – Electrical tracking
over contaminated insulator
Arcing – Electrical breakdown of a gas
that produces plasma discharge
PD and Noise
局放与背景噪声
Every substation or test point has background noise in the
frequency range of TEV devices.
The majority of background noise is within
acceptable ranges and will not interfere with TEV signals.
However, some
noise will be high enough to interfere with correct measurement of PD
activity
Common causes of background noise:
-
Fluorescent lighting inside
substations
Can generate high noise signals very local to measurement point
Simple to remove -
Induced EMC noise from local equipment,
e.g. Transformers
Difficult to remove
Usually lower level -
Air Conditioning or environmental
controls
Easy to remove - Differentiating between PD and Noise is the KEY to effective PD detection. The LECOM PD-LSGS has an in-built noise rejection method;
- Pulses per cycle:
- The LECOM PD-LSGS has a built in Noise rejection system. Informing the user when detected pulses are too frequent in the power cycle to be PD.
-
When the LECOM PD-LSGS detects noise, the
screen will
Alternate between a Noise warning and the dB
Reading detected.
The test systems will identify noisy
environments.
Confirm this by placing the device within the substation but
away from the switchgear:
– On cabinets
– Metal panels
– etc
It is important to then attempt to
remove the noise:
– Check the common sources
Most noise will fall within acceptable limits (that is < 30dB)
Noise higher than 30dB that cannot be removed should be investigated by a LECOM PD-LSG1 device to assess the pattern in the power cycle
This will help conclude if it is noise, as well as often allowing the user to see the PD within the noise
Signs of PD 局放产生后有什么现象出现
– Smell of
Ozone. Ozone:
burning wire smell; spark smell; metallic; battery smell
–
Actual evidence:
PD and Switching
PD most likely to occur during switching
It is essential to test before switching.
- If PD is present, manual switching must not take place.
- Consult your companies policy and procedures for whether remote switching should take place
Evidence and effects of PD 局放导致的影响
Electrical trees
Surface tracking
Carbonisation
PD Detection in Cables 电缆的局放检测